Specification
Model | UPS FT-315 | UPS FT-3124 | UPS FT-3164 | UPS FT-325 | |
---|---|---|---|---|---|
Rated capacity | 100K | 120K | 160K | 200K | |
The efficiency of the whole machine | 94%; On-Line double conversion design | ||||
Enter | Voltage | 415/240V or 400/230V or 380/220V (three-phase four-wire), also can be specially designed according to requirements | |||
Voltage range | 208V~478V @ <70% load; 305V~478V @ 100% load | ||||
Frequency | 50Hz or 60Hz (automatic detection) | ||||
Frequency range | 40~70Hz | ||||
Work factor improvement | Under ≧0.99@100% load, it can avoid interference with the operation of other instruments | ||||
Harmonic Distortion (THDi) | <3% | ||||
Output | Rated voltage | 415/240V or 400/230V or 380/220V (three-phase four-wire), also can be specially designed according to requirements | |||
Rated frequency | 50Hz or 60Hz | ||||
Stability | rated voltage ± 1%; rated frequency ± 0.1Hz | ||||
Waveform | Pure sine wave | ||||
Crest ratio | 3: 1 | ||||
Power factor | 0.8 (optional 0.9 model) | ||||
Harmonic distortion | ≦ 2% @ under linear load; ≦ 4% @ under non-linear load | ||||
Conversion time | Zero conversion | ||||
Battery | Type | Lead-acid, water-free and maintenance-free closed type | |||
Discharge method | Configure the battery pack according to customer needs to meet the discharge time | ||||
Panel test | The battery self-test can be performed directly through the LCD panel | ||||
Protection circuit | With battery short-circuit, over-charging and discharging, and battery overheating protection | ||||
Operation tips | LED lights | With normal mains power, bypass power supply, UPS operation, battery supply and UPS failure lights | |||
LCD panel | With UPS status and operation instructions, including input/output: voltage/current/frequency/actual power/apparent power load: capacity/percentage, battery: voltage/current/capacity and UPS fault display records (up to 4000 records) |
||||
Alarm sounds | Battery discharge: beep every two seconds; battery low: beep every half second; output overload: beep every second; UPS abnormal: long beep | ||||
Display panel | The 10.4-inch touch-type color display panel makes it easier and faster to operate the UPS | ||||
Panel monitoring | The LCD panel can record abnormal voltage/frequency and load warning range according to user settings. | ||||
Communication interface | Standard configuration | RS-232/ USB/Smart card slot | |||
Optional | The smart card slot can be installed: RS-232/USB/SNMP/AS-400/ModBus, etc. | ||||
Machine function | Modularization | The whole machine adopts modular design, which has achieved the purpose of quick maintenance and convenient replacement | |||
shared battery pack | The shared battery pack design can ensure the average battery charge | ||||
Password maintenance management | In order to avoid operation by non-maintenance and management personnel, the LCD panel can set a password by itself. When the system is modified or the UPS is turned on, the correct password must be logged in to operate | ||||
Across cabinets in parallel | Support the parallel connection of cabinets of the same type, which can increase capacity or redundant use according to client design | ||||
Overload capacity | 101%~110% supply for one hour; 111%~125% supply for ten minutes; 126%~150% supply for one minute; >151% supply 200msec and then switch to bypass. After the overload condition disappears, the system will automatically switch back to the inverter power supply mode. | ||||
Warning display | With buzzer sound and panel display dual prompts | ||||
Protection circuit | With output short-circuit, UPS leakage, input lightning surge protection, over-temperature protection and overload protection | ||||
ECO mode | Provide ECO power saving mode, increase the efficiency to 98%, and achieve the purpose of energy saving and power saving | ||||
Automatically turn on | The battery startup voltage can be set through the panel. When the power is turned off after a power failure, the system will automatically charge to the set battery voltage and then automatically turn on | ||||
Other functions | With non-interrupted manual maintenance bypass function. UPS can be repaired without interrupting the back-end load | ||||
Web/SNMP management interface | Add SNMP network management card to remotely manage UPS | ||||
Temperature detector | Optional temperature detector, with expansion card slot for ambient temperature detection | ||||
Monitoring software | Support Windows2000/2003/XP/Vista/2008, Windows 7/8, Windows Server 2012, Linux, Unix and Mac systems | ||||
Safety certification | With the Commodity Verification Registration Certificate (BSMI) of the Bureau of Standards, Metrology and Inspection of the Ministry of Economic Affairs, CNS14843-1 (93 version) and CNS14757-2 (99 version) | ||||
Noise (distance one meter) | ≦73dBA | ||||
Using environment | Temperature/Humidity | 0℃~40℃; 0%~95% (non-condensing) | |||
Size• length x width x height (mm) | 940 x 570 x 1015 | 995 x 570 x 1455 |
*If there is any change to this product, a specification confirmation will be attached separately.